AN901Multifunction time relay, 1 changeover contact, 14 functions, 0.1 s to 10 days
NET PRICE (plus VAT)
21.87 €
Offline: 23.14 €
GROSS PRICE (incl. VAT)
26.02 €
Offline: 27.53 €
Incl. 5.50 % online discount
200+ in stock!
Base price: 1 Stück = 21.87 €
Overview
- Universal multifunction time relay with 14 timing functions and 8 time ranges
- Very wide time range from 0.1 seconds to 10 days
- 1 changeover contact
- AC/DC supply
- Immediate activation of the selected function – no need to switch off the supply
- Made in Europe
Description
The AN901 is a multifunction time relay for demanding control and automation tasks. With 14 different timing functions – including on-delay and off-delay, pulse generation and cyclic operating modes (optionally with or without using the control contact) – it offers maximum flexibility for a wide range of applications. Eight time ranges from 0.1 seconds to 10 days reliably cover both very short switching times and extremely long intervals.The multifunction time relay has a powerful changeover contact. The universal supply input (12…240 V AC/DC) enables operation in many different systems without additional adjustments.
Function and time range can be changed quickly during operation without restart or switching off the supply voltage. The compact 17.5 mm DIN-rail design, high-quality electronics and manufacturing in Europe ensure long service life, high operational reliability and easy mounting on 35 mm DIN rails in accordance with DIN EN 60715.
Technical data AN901
Time functions
E – On-delay
E(S) – On-delay, time measurement can be stopped via contact S
Wu - Switch-on for the set time (pulse function)
Bp - Symmetrical cyclic operation, pause first
Wu(S) - Switch-on for the set time, time measurement paused while S is closed
Bp(S) - Symmetrical cyclic operation, pause first, T measurement paused while S is ON
Bi - Symmetrical cyclic operation, pulse first
Bi(S) - Symmetrical cyclic operation, pulse first, T measurement paused while S is ON
R - Off-delay with control contact S
Ws - Single pulse for the set time, triggered by closing S
Wa - Switch-on for the set time, triggered by control contact S
Esa(R) - On- and off-delay, controlled by S on/off, with reset
E(R) - On-delay with reset function
Wu(R) - Switch-on for the set time (pulse function) with reset function
1 min
1 s
1 h
10 h
10 s
10 min
1 Day
10 Days
0,1 ... 1
For more details on the time functions and their diagrams, please refer to the instruction manual.
E(S) – On-delay, time measurement can be stopped via contact S
Wu - Switch-on for the set time (pulse function)
Bp - Symmetrical cyclic operation, pause first
Wu(S) - Switch-on for the set time, time measurement paused while S is closed
Bp(S) - Symmetrical cyclic operation, pause first, T measurement paused while S is ON
Bi - Symmetrical cyclic operation, pulse first
Bi(S) - Symmetrical cyclic operation, pulse first, T measurement paused while S is ON
R - Off-delay with control contact S
Ws - Single pulse for the set time, triggered by closing S
Wa - Switch-on for the set time, triggered by control contact S
Esa(R) - On- and off-delay, controlled by S on/off, with reset
E(R) - On-delay with reset function
Wu(R) - Switch-on for the set time (pulse function) with reset function
1 min
1 s
1 h
10 h
10 s
10 min
1 Day
10 Days
0,1 ... 1
For more details on the time functions and their diagrams, please refer to the instruction manual.
Outputs / inputs
Yes
Control signal
1
Relay 250 V AC1 / 24 V DC / 16 A
2
No
Control signal
1
Relay 250 V AC1 / 24 V DC / 16 A
2
No
Electrical data
± 10%
=< 1,5 W (DC)
4 A (240 V AC, 24 V DC); resistive load
1
16
> 0.5 × 10⁵ cycles @ 16 A, 250 V AC
12 ... 240 V AC/ DC
Direct voltage (DC)
Alternating voltage (AC)
III
=< 1,5 W (DC)
4 A (240 V AC, 24 V DC); resistive load
1
16
> 0.5 × 10⁵ cycles @ 16 A, 250 V AC
12 ... 240 V AC/ DC
Direct voltage (DC)
Alternating voltage (AC)
III
Mechanical data
DIN-rail
Screw terminals: 0.25 ... 2.5 mm²
90 x 17,5 x 64,6 mm
> 3 × 10⁷ cycles
Screw terminals: 0.25 ... 2.5 mm²
90 x 17,5 x 64,6 mm
> 3 × 10⁷ cycles
Accuracy
< ± 0.5%
± 0,05% / °C
± 5%
AC : < 400 ms / DC : < 150 ms
± 0,05% / °C
± 5%
AC : < 400 ms / DC : < 150 ms
Ambient conditions
-20 °C
50 °C
85 %
IP20
50 °C
85 %
IP20
Additional information
2 x LED
Operation: LED, green
Function: LED, yellow
Time measurement: LED, green, flashing
DIN EN 61000-4-2 ESD
DIN EN 61000-4-3 HF radiated
DIN EN 61000-4-4 burst
DIN EN 61000-4-5 surge
DIN EN 61000-4-6 HF grid-bound
CE
cULus
0.065 kg
PL
Operation: LED, green
Function: LED, yellow
Time measurement: LED, green, flashing
DIN EN 61000-4-2 ESD
DIN EN 61000-4-3 HF radiated
DIN EN 61000-4-4 burst
DIN EN 61000-4-5 surge
DIN EN 61000-4-6 HF grid-bound
CE
cULus
0.065 kg
PL
Drawings


A1: Power supply (AC / L+ DC)
A2: Power supply (AC / L- DC)
S: Control signal
15: Relay (common contact)
18: Relay (normally open contact)
16: Relay (normally closed contact)
25: Relay (common contact)
26: Relay (normally closed contact)
28: Relay (normally open contact)
Downloads